Notice of deficiencies, first review
The application noted above has been examined and cannot be approved as submitted. The following items must be addressed. A revised submission will be placed in the queue in the order received.
- 01 ZONING Side yard setback scales at 1.10 m. Minimum required is 1.20 m. Revise or apply for minor variance. By-law, s. 10.20.40
- 02 OBC 9.9 Basement bedroom window not dimensioned. Egress opening cannot be confirmed from the sheets provided. Div. B, 9.9.10.1
- 03 OBC 9.10 Fire separation between garage and dwelling unit not specified on plans or in the assembly schedule. Div. B, 9.10.9.16
- 04 ZONING Lot coverage not provided. Area summary gives gross floor area only. Provide coverage calculation. By-law, s. 10.10.40
- 05 STRUCT Beam sizes noted without material or species and grade. Specify, or provide engineered design. Div. B, 9.23.4